eyc-thm06-industrial-grade-high-temperature-multi-function-dew-point-transmitter.png
Feature : Adaptation to high temperature and high humidity conditions or harsh environments such as chemical pollution & condensation
Input : ​capacitive humidity sensor & Pt100
Measurement range : ​-40 ... +120°C ;
Customized up to 150°C (Optional) ;
0 ... 100%RH (Non-condensing) ; -50 ... +60 dp°C
Output: ​4 ... 20 mA / 0 ... 10 V / RS-485
Signal connection : 3-wire
Accuracy :±0.15°C+0.002°C x t actual ;
0 ... 100%RH (Non-condensing) ; ±3dp°C ± (0.02%F.S./°C)
●Additional option:( ILAC/TAF ) Test report - Standard calibration laboratory ( TAF accreditation:3032, complying with ISO/IEC 17025 )
TAF has mutual recognition arrangement with ILAC MRA
Model : eYc THM06 

Input : Capacitive humidity sensor & Pt100
Measurement range :
Temperature : -40°C ... +120°C ; customized up to 150°C (Optional) ; 
Humidity : 0 ... 100%RH (Non-condensing)
Dew point : -50 ... +60 dp°C
Absolute humidity : 0 ... 32767 ppm(v)
Signal connection : 4 ... 20 mA / 0 ... 10 V / RS-485
Signal connection : 3-wire
Accuracy :
Temperature : ±0.15°C+0.002°C x t actual
Humidity : 0 ... 100%RH (Non-condensing)
Dew point : ±3 dp°C ± (0.02%F.S. / °C)
Reaction time: t90 (Temperature: +25°C) < 30 seconds (SUS sintered filter)
Load resistance : current output : ≦ 500Ω / voltage output : ≧ 10KΩ
Medium : Air, or medium compatible with stainless steel
Operating environment :
Temperature : Body : -20 ... +60°C ; probe : -40 ... +120°C
Humidity : Body : 0 ... 90%RH (Non-condensing)
S.S. Proof pressure for probe : 10 bar (-40 ... +120°C)
Operating power : DC 24±10% V
Electrical connections : M12 metal connector
Installation : Metal quick connector
IP Rating : IP67
Electrical protection : ▪ Polarity reversal protection ▪ Over-voltage ▪ Short-circuit
Housing material : SUS304
Notes: 1. No display (Standard) with display (Optional).
Notes: 2. Probe size: 50 / 100 / 150 mm (Standard), other lengths can be customized.