SS housing, all-in design with anti-condensation function and good heat dissipation.
Good measuring repeatability and anti-interference.
Input:Pt100
Output:DC 4 ... 20 mA;2-wire
Accuracy:±0.5% of F.S.
Temperature range:-50 ... + 50°C / -50...0°C / 0 ... 50°C / 0 ... 100°C / 0 ... 200°C or special range
●Additional option:( ILAC/TAF ) Test report - Standard calibration laboratory ( TAF accreditation:3032, complying with ISO/IEC 17025 )
TAF has mutual recognition arrangement with ILAC MRA
Tham khảo từ trang https://www.eyc-tech.com/
Model : eYc TP04

Input:Pt100
Pt100 sensor current:<0.8mA
Output:DC 4 ... 20 mA(2-wire)
Accuracy:±0.5% of F.S.
 Load resistance:≦(Supply voltage - 8 V) / 0.02 A Ω
Output calibration(ZERO & SPAN) adjustment range:
ZERO adjustment range : ± 10  %
SPAN adjustment range : ± 10  %
Power supply:DC 10 ... 30 V
IP rating:IP65