Voltage or current outputs, optional passive temperature output
Input:MEMS sensor
Output:4 ... 20 mA / 0 ... 10 V
Signal connection:3-wire
Accuracy:± 0.5°C / ±5%RH(30 ... 80%RH)
Measuring range:0 ... 50°C / 0 ... 100%(Non-condensing)
●Additional option:(ILAC/TAF)Test report-Standard calibration laboratory (TAF accreditation:3032, complying with ISO/IEC 17025)
TAF has mutual recognition arrangement with ILAC MRA

Model : eYc THS130THS140 
 

Sensor type:MEMS sensor
Passive T-sensor(3-wire):Pt100 Class A;Pt1000 Class A
Measuring range:0 ... 50°C / 0 ... 100%RH(Non-condensing)
Output:4 ... 20 mA / 0 ... 10 V
Signal connection:3-wire
Warm-up time:<2 min;Stable time 20 min
Response time:t63(15°C to 45°C / 33 to 75%RH)≦ 10 sec
Sampling time:About 3 sec
Temperature influence:Max.-0.15%RH/°C(0°C ... 80°C)
Load resistance:Current<250 Ω;Voltage≧10 KΩ
Accuracy(at 25°C):±0.5°C / ±5%RH(30 ... 80%RH)
Medium:Air
Operating Temp.:0 ... + 50°C
Operating Humid.:0 ... 100%RH(Non-condensing)
Storage Temp.:-20 ... +60°C
Power supply:DC 19 ... 35 V & AC 24 V±10%
Current consumption:DC:Max. 80 mA / AC:Max. 150 mA
Electrical connection:3-wire:4P connector / Passive T-sensor:3P connector
Installation:Indoor:Wall mount;Duct:Flange
IP rating:IP54
Electrical protection:■ Polarity protection ■ Over-voltage ■ Short circuit
Certification:CE
Housing material:PC(PC-110)(UL94V-2)
Weight:THS130:113 g;THS140:135 g